Grounding Electrode Conductor (GEC) — Definition & Formula Links

The conductor tying a service’s grounded conductor to the earth electrode system, sized from the service-entrance conductors per NEC Table 250.66.


Updated August 22, 2026

The grounding electrode conductor connects the service’s grounded conductor to the earth electrode system, and it answers different physics than its cousin the EGC: the GEC handles lightning and surge gradients, not breaker-tripping fault current. It is sized from the largest ungrounded service-entrance conductor per NEC Table 250.66 — a typical 200 A residential service on 2/0 or 3/0 copper lands in the table’s third row, a 4 AWG copper or 2 AWG aluminum GEC. Parallel service sets are handled by the table note on equivalent area: add the circular-mil areas on one phase, so two 4/0 copper conductors per phase are 423,200 cmil, the "over 350 through 600 kcmil" row, and the GEC is 1/0 copper even though each individual conductor is only 4/0.

Three reliefs in 250.66(A)–(C) cap the size by electrode type: a GEC that is the sole connection to a rod, pipe, or plate electrode never needs to be larger than 6 AWG copper — the reason 6 AWG bare copper to the ground rods is so common — a concrete-encased electrode caps at 4 AWG copper, and a ground ring follows its ring conductor. Table lookups are a code starting point rather than the whole check: installation conditions and local amendments can change the answer, and the full Article 250 review still applies.

Try the Calculators

Sources & Further Reading

  • NEC 2023 (NFPA 70) Table 250.66 — grounding electrode conductor for AC systems, keyed to the largest ungrounded service-entrance conductor or equivalent parallel area
  • NEC 2023 250.66(A)–(C) — electrode-type reliefs: rod/pipe/plate max 6 AWG Cu, concrete-encased max 4 AWG Cu, ground ring per the ring conductor