Grounding Resistance

Estimate the resistance to earth of a single driven rod, multiple rods in parallel, or a ground grid, and compare against the 25-ohm NEC and 5-ohm targets.


IEEE Std 142 / NEC 250.53

Electrode Type

Soil & Electrode

Ω·m
m
mm

Results

33.49Ω
System resistance
33.49Ω
Single-rod resistance
No
Meets 25 Ω (NEC)
No
Meets 5 Ω target

About Grounding Resistance Calculator

The grounding resistance calculator estimates the resistance to earth of common grounding electrodes: a single driven ground rod, several rods connected in parallel, and a buried ground ring or grid. It uses the classical Dwight equation recommended in IEEE Std 142 (the Green Book) for the single rod and applies a spacing efficiency factor to the parallel arrangement so the result reflects the mutual coupling between closely spaced rods.

Enter the soil resistivity in ohm-metres, the rod length in metres, and the rod diameter in millimetres, and the tool reports the single-rod resistance, the resistance of the chosen electrode system, and whether it satisfies the 25-ohm threshold of NEC 250.53 and the tighter 5-ohm target often used for sensitive equipment. Soil resistivity dominates the result and varies widely with moisture and soil type, so use a measured value where possible.

How It Works

  1. Pick the electrode type: a single rod, multiple parallel rods, or a ground ring/grid.
  2. Enter soil resistivity (ohm-m), rod length (m), and rod diameter (mm). For parallel rods add the rod count and centre-to-centre spacing; for a grid add the enclosed area and total buried conductor length.
  3. The single rod uses the Dwight equation R = rho/(2*pi*L) * (ln(4L/a) - 1) with a = rod radius.
  4. Parallel rods apply R_n = R_single/(n*F), where F (0-1) is a spacing efficiency that rises with spacing and falls as rods are added. The grid uses R = rho/(4r) + rho/L_total with r the equivalent radius of the enclosed area.

Worked Example

A single copper-clad rod is driven into soil with resistivity rho = 100 ohm-m. The rod is L = 3 m long and d = 16 mm in diameter, so its radius a = 0.008 m. The Dwight equation gives R = 100/(2*pi*3) * (ln(4*3/0.008) - 1) = 5.305 * (7.3132 - 1) = 33.49 ohm, which exceeds the 25-ohm NEC limit. Driving four such rods in parallel at 3 m spacing with an efficiency F = 0.70 gives R = 33.49/(4*0.70) = 11.96 ohm, comfortably below 25 ohm.

Formulas

Single driven rod (Dwight equation)
R = rho / (2 * pi * L) * (ln(4 * L / a) - 1)
Multiple rods in parallel
R_n = R_single / (n * F)
Ground ring / grid estimate
R = rho / (4 * r) + rho / L_total, r = sqrt(A / pi)

Standards & References

  • IEEE Std 142 (Green Book)
  • IEEE Std 80 (grounding of substations)
  • NEC 250.53 (25-ohm rod requirement)

Frequently Asked Questions

Why does the 25-ohm value matter?

NEC 250.53(A)(2) requires a single made electrode (rod, pipe, or plate) to achieve 25 ohm or less; if it does not, a second electrode must be added. The 25-ohm figure is a code minimum, not a performance target for equipment grounding.

What soil resistivity should I use?

Soil resistivity varies enormously, from under 50 ohm-m for wet clay to several thousand ohm-m for dry sand or rock. Use a measured Wenner four-pin value for the site; the calculation is directly proportional to resistivity, so this input dominates the answer.

Why is doubling the rods not halving the resistance?

Rods placed close together share overlapping soil volumes, so they partly compete for the same current paths. The spacing efficiency factor F captures this: at typical spacing four rods behave like about 2.8 independent rods, which is why R_n = R_single / (n * F) rather than R_single / n.

Is this a substitute for a measured ground test?

No. It is a design-stage estimate. The actual resistance depends on seasonal moisture, soil layering, and installation quality, so always confirm with a fall-of-potential or clamp-on ground resistance measurement after installation.