AWG Wire Gauge Chart — Diameter, Resistance & NEC Ampacity

AWG 14 to 500 kcmil conductor sizes with diameter, circular-mil area, and 75 °C copper resistance per NEC Chapter 9 Table 8, plus NEC 310.16 ampacities.


Updated August 16, 2026

American Wire Gauge runs backwards: smaller numbers are bigger wires, and above 4/0 AWG sizes switch to thousands of circular mils (kcmil). A circular mil is the area of a 0.001 in diameter circle, so the cmil column is exactly the squared diameter of an equivalent solid conductor in mils — which is why 250 kcmil means 250,000 cmil by definition. Every three gauge steps halves the resistance; every ten steps changes the area by a factor of ten.

The first table gives the physical constants for stranded, uncoated copper from NEC Chapter 9, Table 8 — the values used for voltage-drop and fault calculations. The second table is NEC Table 310.16: allowable ampacity for not more than three current-carrying conductors in raceway, cable, or earth at 30 °C ambient. It is rendered directly from the same data our conductor ampacity calculator uses, so the chart and the calculator always agree.

Remember that 310.16 is a starting point, not a final answer: ambient temperatures other than 30 °C, more than three current-carrying conductors, continuous loads (125%), and termination temperature limits all modify the usable value. The ampacity calculator applies those corrections in the code-prescribed order.

Conductor Properties (NEC Chapter 9, Table 8 — Stranded Copper)

SizeArea (cmil)Area (mm²)Ø stranded (in)Ø stranded (mm)DC resistance, Cu 75 °C (Ω/1000 ft)
14 AWG4,1102.080.0731.853.14
12 AWG6,5303.310.0922.321.98
10 AWG10,3805.2610.1162.951.24
8 AWG16,5108.3670.1463.710.778
6 AWG26,24013.300.1844.670.491
4 AWG41,74021.150.2325.890.308
3 AWG52,62026.670.2606.600.245
2 AWG66,36033.620.2927.420.194
1 AWG83,69042.410.3328.430.154
1/0 AWG105,60053.490.3729.450.122
2/0 AWG133,10067.430.41810.620.0967
3/0 AWG167,80085.010.47011.940.0766
4/0 AWG211,600107.20.52813.410.0608
250 kcmil250,0001270.57514.610.0515
300 kcmil300,0001520.63016.000.0429
350 kcmil350,0001770.68117.300.0367
400 kcmil400,0002030.72818.490.0321
500 kcmil500,0002530.81320.650.0258

Class B stranded, uncoated copper. DC resistance at 75 °C per NEC Chapter 9, Table 8; kcmil areas in cmil are definitional (1 kcmil = 1,000 cmil). Solid conductors of the same size have slightly smaller diameters and marginally lower resistance.

Allowable Ampacity (NEC Table 310.16, 30 °C Ambient)

SizeCu 60 °C (A)Cu 75 °C (A)Cu 90 °C (A)Al 60 °C (A)Al 75 °C (A)Al 90 °C (A)
14 AWG152025
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350

Not more than three current-carrying conductors in raceway, cable, or direct-buried, 30 °C (86 °F) ambient, per NEC 2023 Table 310.16. Aluminum is not produced in 14 AWG for this table. Apply ambient correction (310.15(B)(1)), bundling adjustment (310.15(C)(1)), the 125% continuous-load factor, and termination limits (110.14(C)) before selecting a conductor.

Sources & Further Reading

  • NEC (NFPA 70) 2023, Chapter 9, Table 8 — Conductor Properties
  • NEC (NFPA 70) 2023, Table 310.16 — Allowable Ampacities (as encoded and verified in the conductor ampacity calculator)

Frequently Asked Questions

Which ampacity column am I allowed to use?

The column matching your conductor insulation rating (e.g. THHN is 90 °C), but the final value can never exceed what the termination temperature allows — most breakers and lugs are rated 75 °C, and circuits 100 A and under often default to 60 °C terminations per NEC 110.14(C). The 90 °C column is mostly useful as the starting point for derating.

Why does 12 AWG copper show 30 A but get breakered at 20 A?

NEC 240.4(D) caps the overcurrent protection for 14, 12, and 10 AWG copper at 15, 20, and 30 A respectively regardless of the table value. The higher table numbers still matter: derating for ambient or bundling starts from the insulation-rated column, and the small-conductor cap is applied at the end.

How much does resistance change with temperature?

Copper resistance rises about 0.39% per °C. Table 8 lists DC resistance at 75 °C; at 20 °C the same conductor is roughly 18% lower. For AC circuits 250 kcmil and larger, skin effect adds measurably — NEC Chapter 9 Table 9 lists effective AC resistance for those cases.

What is a circular mil and why does the code use it?

One circular mil is the area of a circle 0.001 in across, so area in cmil equals the mil diameter squared — no π needed. It makes wire math convenient: the classic K-factor voltage-drop formula (K ≈ 12.9 Ω·cmil/ft for copper at 75 °C) divides directly by the cmil area from this chart.

Try the Calculators